4. Programming
496964 Page 63
Value Type Description
02 Fire (FR) Smoke or heat detectors connected to FR type zones
cause the speakers to give a distinctive fire signal
(internal sounders pulsing "Dee Dah Dee Dah..."). Fire
alarms always operate, whether the system is set or
unset, and always trigger communications if fitted. Fire
zones can be allocated to one or more partitions in a
partitioned system (A–D attributes on page 67) but
these attributes are not available in a single system.
03 Normal
Alarm (NA)
A zone programmed as "Normal Alarm" will start an
alarm when the system is set.
04 24-hour
Zone (24)
This zone causes an internal alarm if violated when the
system is unset, and a full alarm if the system is set. If
the Installer programs 24-hour zones with "Omit Allow",
the user can omit 24-hour zones in Day mode. The
control unit reinstates all 24-hour zones if anyone sets
the system.
05 Final Exit
(FE)
Zones of this type must be the first to be activated on
entry. You can use zones of this type to set the system
using the Final Door Set exit mode. Use Command 39
to set the exit mode for the zone (page 74). Use zone
attribute X7 to select an entry timer for the zone (page
67) and Commands 201–4 (page 116) to set up the
entry timers.
06 Entry Route
(ER)
Use this zone type for detectors sited between the
Final Exit door/detector and a keypad. If an "Entry
Route" zone is violated when the system is set, an
alarm will occur. If the Entry/Exit timer is running when
an Entry Route zone is violated, no alarm occurs until
the Entry/Exit timer expires. Use zone attribute X7 to
select an entry timer for the zone (page 67) and
Commands 201–4 (page 116) to set up the entry
timers.
07 Shock
Analyser
(SA)
You can apply this zone type to zones 1 to 4. The
system will not accept this type for zones 5 to 40. Use
zone attribute X7 to set the sensitivity for the zone
(page 67).