4. Programming
496929 Page 47
Set o/p 3 ABCD, select the level(s) in which the output will be active
toggle abcd keys to select level on /off.
Set o/p 4 ABCD, select the level(s) in which the output will be active
toggle abcd keys to select level on /off.
172 Unset o/p 1 Time, select a time in the range 01-12 seconds
Unset o/p 2 Time, select a time in the range 01-12 seconds
Unset o/p 3 Time, select a time in the range 01-12 seconds
Unset o/p 4 Time, select a time in the range 01-12 seconds
173 Unset o/p 1 ABCD, select the level(s) in which the output will be active,
toggle abcd keys to select level on /off.
Unset o/p 2 ABCD, select the level(s) in which the output will be active,
toggle abcd keys to select level on /off.
Unset o/p 3 ABCD, select the level(s) in which the output will be active,
toggle abcd keys to select level on /off.
Unset o/p 4 ABCD, select the level(s) in which the output will be active,
toggle abcd keys to select level on /off.
174 Fire o/p 1, Select as on if O/P 1 is to respond if a Fire alarm occurs
Fire o/p 2, Select as on if O/P 2 is to respond if a Fire alarm occurs
Fire o/p 3, Select as on if O/P 3 is to respond if a Fire alarm occurs
Fire o/p 4, Select as on if O/P 4 is to respond if a Fire alarm occurs
175 PA o/p 1, Select as on If O/P 1 is to respond if a PA alarm occurs
PA o/p 2, Select as on If O/P 2 is to respond if a PA alarm occurs
PA o/p 3, Select as on If O/P 3 is to respond if a PA alarm occurs
PA o/p 4, Select as on If O/P 4 is to respond if a PA alarm occurs
Note: For options 174 to 175 use 1 for ON and 0 for OFF.