4. Programming
74 496792
Report Mode (Command 131)
SIA reports are called ‘Telegrams’. Each telegram contains the site identifica-
tion number (normally six digits long) and relevant event information. The
amount of information reported depends on the SIA mode you select: Basic,
Summary, Intermediate, or Full. Figure 24 shows the types of report for each
mode. Use the table to decide which mode is appropriate for the installation.
Option 0 Basic
Option 1 Summary
Option 2 Intermediate
Option 3 Full
The system also provides a “custom” mode which allows any combination of
event information. However, you must use <Downloader> to create the
combination required.
SIA alarm transmissions will take considerably more telephone time than
Scancom Fast format since the system transmits extended alarm data to the
ARC.
Note: The control unit delays reporting/loging either mains loss, or exiting engineer-
ing with mains loss, by 15-18 min (chosen randomly). The control unit delays
reporting/loging either mains restore, or exiting engineering with mains re-
stored, by 60-90 sec (chosen randomly). If you chose a Scandinavian default in
Command 0 then the control unit waits at least 60 minutes before reporting.
BASIC
Event SIA Code CID Code
ALARM ABORT BC 406
ALARM CONFIRM BV 139
BURG BA 130
DURESS HA 121
EXIT TIMEOUT EA -
FIRE FA 110
GLOBAL TAMPER TA 137
KEYPAD FIRE FC 110
KEYPAD MEDICAL MA 100
KEYPAD PA HA 120
MAN TRIGGER TEST REPORT RX 601
PA TELECOMMAND PA 120
PANIC PA 120
PERIODIC TEST REPORT RP 602
SENSOR TAMPER TA 137
SMOKE DETECTOR ALARM FA 111
ZONE OMIT BB 573
SUMMARY
Event SIA Code CID Code
ARM CL 401
DISARM OP 401
EXPANDER MISSING TA 137
EXPANDER TAMPER TA 137
FIRE RESTORE FR 110‡
LID TAMP TA 137
PANIC RESTORE PR 120‡
PARTN RESET OR 305
PROG MODE END LS 628
PROG MODE START LB 627
RESET OR 305
SMOKE DETECTOR RESTORE FR 111
SOUNDER TAMPER TA 137
SYS TAMPER TA 137
TA (Technical alarm) UA 150‡
TA RESTORE UR 150
TAMPER IN DAY TA -
TAMPER KEYPAD TA 137
TAMPER USER CODE JA 461