Cooper Security i-on 16 Guia do Utilizador Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
i-on30EX
Page 9
Cable Configuration and Length
You can connect up to 10 devices to the
control unit bus. You may connect the
devices either in daisy chain (serially), or in
star (parallel) configuration at the control
unit connector.
Figure 10 Bus Wiring Configurations
For star configurations the cable length
from control unit to the most distant bus
device should be kept short, and should not
exceed 100m. There should be no more
than four arms in the star.
For a daisy chain configuration the total
cable length should not exceed 1,000m.
Bus Termination
The i-on30EX bus uses the RS485 interface.
Because of this the ends of the line in some
configurations may be terminated to
improve performance in electrically noisy
environments or where there are long cable
runs. The control unit. expanders and
keypads have a termination link on their
PCBs (see 16 in Fig 2 for the control unit, 5
in Fig 7 for the keypad, 12 in Fig 8 for the
wired expander and 11 in Fig 9 for the radio
expander). Fitting a jumper to the pins
adds a termination to the cable.
In a daisy chain configuration fit the
termination jumpers in the devices at each
end of the chain (see Fig 10 ).
In a star configuration:
If there are only two arms on the star
then this is the same as a daisy chain
configuration (see “Daisy Chain 1” in
Figure 10). If required fit the
termination jumper at the devices on
the end of each arm.
If there are more than two arms AND
two cables are long while the remaining
cables are short (less than 10m) then it
is possible to terminate at the two
devices on the ends of the long cables.
If there are more than two arms BUT
each cable is more than 10m then DO
NOT fit the termination jumpers on any
of the devices.
Voltage Drop
In order for the system to work correctly,
the voltage at each device must NOT drop
below 10.5V even when running on the
standby battery. Cooper Security
recommend that the voltage at each device
should stay above 12V.
Standard 7/0.2 alarm cable has a
resistance of 8 Ohms per 100m per core.
The voltage drop is calculated using the
following formula: V Drop = Current drawn
x cable length x 0.08 x 2.
Table 1 shows the voltage drop against the
current drawn and cable length.
The shaded area shows where the voltage
drop would cause the bus voltage to fall
from 13.8V to below 12.0V when using a
single core.
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 35 36

Comentários a estes Manuais

Sem comentários