2. Programming Commands
497096, issue 3 Page 23
44: Level/Partition A Exit Time
This command lets you set the Exit Time for Full Set or Partition A.
Option
1 10 seconds
2 20 seconds (default)
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
45: Entry/Exit Tone Volume
In a single system, this command sets the volume of the Entry/Exit tone from
the internal sounder. If you select option 0, the internal sounder emits no tone.
Select a value from 1 (quietest) to 9 (loudest) to set the volume (default 5).
The internal sounder demonstrates the volume when you enter the digit.
Note: In a partitioned system, this command is available only for Partition A.
46: Tamper Alarm Response
In a single system, this command specifies which sounders the control unit
will activate for a Tamper Alarm while the system is unset.
Option
0 Internal sounders only (default)
1 Keypad sounders only
2 Internal and keypad sounders
Note: This command is not available in a partitioned system.
47: Partition A Alarm Response
In a partitioned system, this command specifies which sounders the control
unit will activate for an alarm.
Note: Compliance with PD 6662 / prEN 50131-1: 2004 (see page 85) requires the full
response, option 2 (default).
Option
0 Keypad sounders only
1 Local alarm (internal and external sounders)
2 Full alarm (internal and external sounders, plus communication)
Note: This command is not available in a single system.