Installer Menu Options i-on160
Page 66
On a Security Grade 2 system the ability to reset the alert is
governed by the System Options - User Reset - System Tampers option,
see page 62.
When the system is set:
Detector
output
Response
Mask
(9k1)
The control unit treats a masking event as an alarm condition.
This will signal an unconfirmed alarm or will confirm an
outstanding unconfirmed alarm. The unconfirmed and confirmed
events must be from different detectors.
The ability to reset the system after the alarm is governed by the
System Options - User Reset – Zone Alarms option, see page 61.
Fault
(4k4)
The control unit treats a masking event as a fault, activates any
outputs programmed as General Fault or Masking, and generates
an Alert on the keypads.
On a Security Grade 3 system the Installer must reset the Alert.
On a Security Grade 2 system the ability to reset the alert is
governed by the System Options - User Reset - System Tampers option,
see page 62.
Mask Override
This option controls how the user can respond to a masking event once it is
reported by the control unit. There are two options:
Mask
Override
A User can override a masking fault to set the system
Mask
Inhibit
Set
A User is may not override a maskin
g
fault to set the system. The
system will not set until the masking fault has cleared.
Language
The control unit can use one of several languages in its display. To change the
language select System Options – Language.
Changing the language does not affect any stored names for full/part set,
detectors, outputs or users, and does not change any defaults.
Restore Defaults
Country Defaults
Each country has different settings for PSTN communications and alarm
reporting. You can use this option to select default settings for a given country.
Changing the country does not change the language used by the display.
Staged Defaults
This menu option allows you to default parts of the control unit’s programming,
without affecting the whole system. From within this menu you can choose to
default one or more of the following: